Product name: | GK 80 - perforated |
Manufacturer: | Ecker – Heiz- und Kühlflächensysteme GmbH |
Version: | For perforated gypsum plasterboard ceilings, fine grid approx. 333 mm |
Design: |
Heating element grouted uniformly in heat-conducting aluminium profiles 53 mm wide, with installation brackets that are completely pre-assembled at the factory and these are to be hung between the CD-profiles of the fine grid structure. |
Piping: | Using soft-soldering, compression or plug-in technology |
Plasterboard covering: | Perforated thermal plate 10 mm, with / without graphite component |
|
Technical Data:
Pipe diameter: | 10 x 0,55mm |
Pipe spacing: | 80 mm |
Number of pipe rows: | 3 |
Heat output conforming to DIN 14037 (15 K): | up to 95,3 W/m² |
Active used capacity (theoretical): | max. 70 % |
Weight of heating element: | approx. 8 kg/m² |
Plasterboard covering: Gypsum plasterboards of 10 mm thickness with a thermal conductivity of at least 0.5 W/m²xK
max. heat output in conformance with DIN 14037 (15 K): 95.3 W/m²
Plasterboard covering: Gypsum plasterboards of 10 mm thickness with a thermal conductivity of at least 0.3 W/m²xK
max. heat output in conformance with DIN 14037 (15 K): 82.1 W/m²
References to the Diagram:
German Terms | English Translations |
Heizleistung in W/m2 |
Heat output in W/m2 |
Max. Heizleistung nach DIN 14037 für gelochte GK-Decken |
Max. heat output in conformance with DIN 14037 for perforated gypsum plasterboard ceilings |
Temperaturdifferenz in K | Temperature difference in K (Kelvin) |