Product name: | KS |
Manufacturer: | Ecker – Heiz- und Kühlflächensysteme GmbH |
Version: | For metallic ceiling canopies |
Connection: |
Cooling element comprising copper tube and heat-conducting aluminium profiles grouted uniformly and permanently in the ceiling canopies made of sheet steel (at least 0.7 mm), on acoustic fleece glued all over, with a component temperature of 38 °C. |
Verbindung: |
Using oxygen-barriered plastic and reinforced hoses |
Technical Data:
Pipe diameter: | 10 x 0,55 mm/12 x 0,60 mm |
Width of heat-conducting profile: |
76 - 86 mm |
Pipe spacing: | 100 mm |
Cooling capacity conforming to DIN 14240 (10 K): | up to 129,8 W/m² |
Weight of cooling element: | approx. 8 kg/m² |
Max. cooling capacity conforming to DIN 14240 (8 K): 102.0 W/m²
Max. cooling capacity conforming to DIN 14240 (10 K): 129.6 W/m²
References to the Diagram:
German Terms | English Translations |
Kühlleistung in W/m2 |
Cooling capacity in W/m2 |
Max. Kühlleistungen nach DIN 14240 für Metalldeckensegel |
Max. Cooling capacities conforming to DIN 14240 for metal ceiling canopies |
Temperaturdifferenz in K | Temperature difference in K (Kelvin) |